Application under Section 14 of the Electricity Act, 2003 read with Central Electricity Regulatory Commission (Procedure, Terms and Conditions for Grant of Transmission License and other related matters) Regulations, 2009 for grant of separate Transmission License to POWERGRID KPS2 Transmission System Limited for Inter connection of RE developer’s Dedicated Transmission Line at Khavda Pooling station-2 (KPS-2) under “Regulated Tariff Mechanism” (RTM) mode”

APPLICATION FOR GRANT OF TRANSMISSION LICENSE THROUGH RTM MODE

Form_II_English

Form_II_Hindi

Form_II_Gujarati


KPS2 Transmission Limited hereby submits this application under Section 14 & 15 of the Electricity Act, 2003, Central Electricity Regulatory Commission (Procedure, Terms and Conditions for Grant of Transmission License and other related matters) Regulations, 2009 (hereinafter referred to as “Transmission License Regulations”) to establish Establishment of Khavda Pooling Station.2 (KPS2) in Khavda RE Park on build, own, operate and transfer basis (hereinafter referred to as “the Project”) consisting of the following elements:

  1. Establishment of 765/400 kV, 4x1500MVA, KPS2 (GIS) with 2x330 MVAR 765 kV bus reactor and 2x125 MVAR 400 kV bus reactor.
  • 1500MVA, 765/400kV ICT- 4 nos.
  • (13x500 MVA including one spare unit)
  • 765 kV ICT bays – 4 nos. 400 kV ICT bays – 4 nos. 765 kV line bays – 2 nos. 400 kV line bays – 3 nos.
  • (3 no. of bays considered at present, one each for NTPC, GSECL & GIPCL)
  • 1x330 MVAr, 765 kV bus reactor-2
  • (7x110 MVAr, including one spare unit)
  • 765 kV reactor bay – 2 1x125 MVAr 400 kV bus reactor-2
  • 400 kV reactor bay – 2
  • 765 kV bus sectionalizer bay – 2
  • 400 kV bus sectionalizer bay – 2
  • Adequate space for future expansion of 5x1500 MVA 765/400 kV ICT’s
  • Bus sectionalizer at 765kV & 400kV.
  • On each bus section, there shall be 2x1500MVA 765/400kV ICTs, 1x330MVAr, 765 kV & 1x125MVAr 420kV bus reactor with space for future expansion.
  • Bus sectionalizer at 765 kV level shall normally be closed and bus sectionalizer at 400 kV level shall normally be open.

 

Future provisions:

  • Space for 765/400 kV ICTs along with bays: 5 nos. 765kV line bay with switchable line reactor: 10 nos.
  • 400kV line bay with switchable line reactor: 12 nos.
  • 8000MW, ±800kV HVDC Converter station (LCC).
  • To take care of any drawal needs of area in future: 400/220 kV ICT: 2 nos.
  • 220 kV line bays: 4 nos.